Automated Controls & Engineering

Type H Recloser
AUTOMATED CONROLS & ENGEINEERING TYPE 4H RECLOSER

Trip-Coil Continuous Current (amps) Minimum Trip Current (amps) Interrupting Current
(rms symmetrical amps)
  @ 4.8 @ 8.32 @ 14.4
5 10 200 200 200
10 20 400 400 400
15 30 600 600 600
25 50 1000 1000 1000
35 70 1400 1400 1400
50 100 2000 2000 2000
70 140 2800 2500 2000
100 200 3000 2500 2000
WEIGHTS AND OIL CAPACITY

Description Recloser Type
  V4E H 4H / V4H L V4L
Weight, without oil (lb) 147 55 76 106 142
Weight, with oil (lb) 210 85 114 159 205
Oil capacity (gal) 9 1/2 4 5 7 9 1/2

CLICK HERE TO CLOSE THIS WINDOW